Becsys5 Installation And Technical Manual Info
BECSys5 Installation and Technical Manual
Document Version: 1.0
Applicable To: BECSys5 Series Controllers (B5-100, B5-200, B5-300)
Audience: Certified HVAC/BMS Technicians, System Integrators, Commissioning Engineers
9.2 Factory Reset
To reset to factory defaults (preserves IP address? – No, resets to DHCP): becsys5 installation and technical manual
- Power off.
- Press and hold physical "RESET" button (recessed) on MCM.
- Power on while holding for 10 seconds.
- Release after STATUS LED flashes orange.
- Default credentials:
admin / admin. License must be re-applied.
Chapter 6: Commissioning and Validation
4.3 Installing I/O Modules
- Remove backplane covers.
- Align module with slot guide.
- Press firmly until ejector latches click.
- Secure with two screws (0.5 Nm).
- Label each slot (e.g., "Slot 2: AI8-U, Chillers").