Becsys5 Installation And Technical Manual Info

BECSys5 Installation and Technical Manual

Document Version: 1.0
Applicable To: BECSys5 Series Controllers (B5-100, B5-200, B5-300)
Audience: Certified HVAC/BMS Technicians, System Integrators, Commissioning Engineers


9.2 Factory Reset

To reset to factory defaults (preserves IP address? – No, resets to DHCP): becsys5 installation and technical manual

  1. Power off.
  2. Press and hold physical "RESET" button (recessed) on MCM.
  3. Power on while holding for 10 seconds.
  4. Release after STATUS LED flashes orange.
  5. Default credentials: admin / admin. License must be re-applied.

Chapter 6: Commissioning and Validation

4.3 Installing I/O Modules

  1. Remove backplane covers.
  2. Align module with slot guide.
  3. Press firmly until ejector latches click.
  4. Secure with two screws (0.5 Nm).
  5. Label each slot (e.g., "Slot 2: AI8-U, Chillers").